About the 9905-372
Environmental specifications for the 9905-372 are:
- Operating temps: –40 to +70 °C (-40 to 158 F)
- Storage temps: –55 to +105 °C (-67 to 221 F)
- Humidity: 95% at 38 °C
- Mechanical shock: US MIL-STD 810C, Method 516.2, Procedures I, II, V
- Electromagnetic susceptibility: ANSI/IEEE C37.90.2; ANSI C37.90.1-1989
- Vibration: US MIL-STD 167, Type I
This device has an Open Delta PT Configuration, a 500 Hz PWM Speed Bias, and a 120 Vac Input Voltage. Extra functions of Woodward model 9905-372 are:
- Built-in diagnostics
- Setup, metering, and diagnostic capability through a handheld programmer terminal
- Automatic generator loading and unloading
- Droop, baseload, and isochronous load control capability
- Reverse power relay.
This model offers phase matching or slip frequency synchronizing. With both methods, a minimum phase difference between generator and bus at actual breaker closure is anticipated by using actual slip frequency and breaker delay values. Model 9905-372 has an automatic dead-bus closure function, where only one DSLC control is granted dead-bus closing permission through locking techniques over the communications network.