About the 8440-3004
Model 8440-3004 is from the easYgen-1000 series produced by Woodward INC, this model is available at AX Control INC. We offer repairs and refurbishment to this model as well, if you are interested in repairing your control with us we also offer a one to three-year warranty.
The control mode can start automatically based on the clock that you are using within the control, if you are using the clock in active day mode it will indicate the day of the month, for example, the number 9 would mean the 9th of every month, it will remain on the 9th for the next 24 hours, this mode could allow for the control to start the engine automatically once a month.
When you are using your control the rated voltage or frequency mains of the control differ, the values for the emergency mode of the control will relate to the generator nominal voltage, and the mains do not have any parameters. You can close the GCB of the control while it is in manual mode, to do so make sure that the generator undervoltage monitoring levels one and two must be enabled so the GCB can be closed.
A battery can be connected to the control, make sure that when doing so that the battery plus side of the battery is connected to one side of the relay while the D+ is connected to the other side and specifically the current limiting resistor, make sure that the current limiting resistor is connected with the correct application, if it is 24 V then it should be 210-240 Ohm.