About the 8440-2055
The easYgen-3000 model 8440-2055 is designed for the cabinet back mounting. There is no built-in HMI with this model. Instead, configuration and operations are managed via PC using ToolKit software.
Part 8440-2055 may be used for both single and multiple unit operations, including mains parallel operation for up to 32 units, for a variety of applications. Four operating modes are available with this genset controller: Automatic, Manual, Stop, and Test. Full control features and additional product specifications may be found in Woodward easYgen-3000 manual 37258P.
Numerous setpoints may be configured to meet the requirements of various applications. The 8440-2055 model offers protection against generator overload or unbalanced load, engine over speed or under speed conditions, engine speed/frequency mismatch, mains phase shift/rotation field issues, and much more.
Speed input is measured using magnetic / switching pickup (50/60 Hz measuring frequency). Part 8440-2055 has discrete I/Os and analog I/Os. Both types of inputs/outputs are configurable. Ten of the twelve alarm outputs are configurable.