About the 5437-1078
Product Model 5437-1078 is a ProTech detection system from Woodward. It’s compatible with hydro, gas, and steam turbines, functioning to safely shut them down. This product uses 2 out of 3 voted architecture, and three non-voted trip relay outputs, allowing for one to fail or be worked on while the others are functioning. Each of the three independent relays has individual alarms.
Model 5437-1078 High-Voltage/Low-Voltage Voted Spare Relay Module for ProTech models -1246, and -1369. In addition to acceleration detection, this safety device also uses open-wire MPU detection and communication with speed readouts of 4-20 mA. The sulfur-resistant conformal coating allows for this safety device to be used in class 3C2 environments. The 5437-1078 is certified as a Safety Integrity Level 3 safety device and can be applied as a stand-alone IEC61508-based device or within an IEC61511-based plant safety system.
Unit 5437-1078 has been discontinued by Woodward, but can still be found through AX Control. AX Control is able to buy and sell, as well as repair, this product. Contact our Sales Team Today for a Free Quote at: