About the F2-02DA-2L
The F2-02DA-2L Analog Output Voltage Module is a 2 channel analog Output Voltage Module. The output range is 4-20 mA. The peak output voltage is 0–5V, 0–10V, ±5V, ±10V. The number of channels is 2. The resolution is 12 bit (1 in 4096). The power budget requirement is 40mA at 5VDC (supplied by the base). The environmental air requirement is no corrosive gases permitted. The operating temperature 0–60°C (32–140°F). The relative humidity 5–95% (non-condensing).
The PLC update rate is 1 channel per scan maximum for the D2-230 CPU and 2 channels per scan maximum for the D2-240/250-1/260 CPUs. The output points required is 12 binary data bits, 2 channel ID bits 16 (Y) output points.
Jumpers on the The F2-02DA-2L (L) Analog Output module are used to select the voltage ranges for each channel. The voltage range of each channel can be independently set.
The F2-02DA-2L Analog Output Voltage Module contains valuable hardware features.
-
The module optically isolates outputs from the PLC to improve signal quality.
-
For improved usability and portability, the terminal block is easily removable to ensure the F2-02DA-2L Analog Output Voltage Module is easily removable without disconnecting wiring.
-
If a DL250-1 or a DL260 CPU is used in the DL205 PLC, both channels can be updated in one scan.
-
The low-power CMOS design requires less than 70mA from an external 12VDC power supply.
When wiring the F2-02DA-2L Analog Output Voltage Module, consider the following information.
-
Use the shortest wiring route.
-
Be sure to use shielded wiring and ground the shield at the transmitter source.
-
To avoid electrical noise, keep away from large motors, high current switches and transformers when planning the wiring route.
-
To avoid damage, route the wires through approved cable housing only. Follow all applicable codes to select the correct housing.