About the F2-02DAS-1
The F2-02DAS-1 Analog Output Voltage Module contains 2 channels. The module is an analog output voltage module. The range 4 and 20 mA is the rated power output.
The output voltage is 0 through 5V and 0 through 10V, ±5V, ±10V at the peak output. The F2-02DAS-1 Analog Output Voltage Module contains 2 channels. The resolution is 12 bit (1 in 4096).
The requirement is 40mA at 5VDC for the budget you can use for power. No corrosive gases permitted is the environmental limit. Temperature must be between 0 and 60°C (32 and 140°F). The relative humidity 5–95% (non-condensing).
The PLC update rate:
12 binary data bits, 2 channel ID bits 16 (Y) output points are the output points that module needs. Loop power supply: 18-32 VDC. To choose the voltage range for the channels, use the jumpers supplied on the unit. Each channel can be configured separately.
The F2-02DAS-1 Analog Output Voltage Module contains valuable hardware features.
-
Isolated analog outputs (channel to channel) and (channel to PLC).
-
Removable terminal block.
-
If a DL250-1 or a DL260 CPU is used in the DL205 PLC, both channels can be updated in one scan.