About the F2-04AD-1
The power budget requirement for the F2-04AD-1, 4-Channel Analog Current Input Module is 110mA (*60mA maximum, 5VDC (supplied by base). The environmental air requirement is no corrosive gases permitted. The operating temperature 0-60°C (32-140°F). The relative humidity 5–95% (non-condensing).
The F2-04AD-1, 4-Channel Analog Current Input Module is a 4-channel analog input voltage module. The input range is 0-5 VDC and 0-10 VDC. The number of channels is 4, single ended (one common). The resolution is 12 bit (1 in 4096) unipolar (0–4096) 13 bit (1 in 8192) bipolar (-4095 – +4095). The PLC update rate is 1 channel per scan maximum (DL230 CPU) 4 channels per scan maximum (DL240/250-1/260 CPU). The input points requirement is 12 binary data bits, 2 channel ID bits, 1 sign/diagnostic bit,1 diagnostic bit 16 point (X) input module.
The F2-04AD-1 can be installed in any slot in a DL230. However, one consideration is that if the module is placed so the input points do not start on a V-memory boundary, the instructions cannot access the data.
The F2-04AD-1, 4-Channel Analog Current Input Module contains valuable hardware features.
-
The analog inputs are optically isolated from the PLC logic.
-
For improved usability and portability, the terminal block is easily removable to ensure the F2-04AD-1, 4-Channel Analog Current Input Module is easily removable without disconnecting wiring.
-
If a DL240, or DL250-1, or DL260 CPU is used, all four channels can be read in one scan.
-
The F2-04AD-1 contains on-board active analog filtering.
-
The F2-04AD-1 contains microcontroller provide digital signal processing.