About the D3-16TD2
Automation Direct's 16 Point, 2 Common DC Powered Output Module was a product manufactured by both Koyo and PLC Direct. The 16 output points on the module are current sinking points. There are two commons so for every 8 points, there is an isolated output common. The output type of the module is an emitter follower NPN transistor. The device weighs 7.1 ounces. There is a removable terminal that gives the module the ability of remote use. There is a logic side status indicator that allows the user to get notified of the issues within the system.
The 16 Point, 2 Common DC Powered Output Module has an operating voltage range the spans from 5 to 24 VDC. The peak input voltage of the device is 40 VDC. The max current is .5 amps per point and 3 amps per common. The maximum leakage current is .01 mA at 40 VDC. The ON voltage drop is 1.5 volts and the minimum load is 1 mA.
There are different maximum inrush currents for different spans of time. For every 20 milliseconds interval the maximum inrush current is 3 amps. For every 100 milliseconds the maximum inrush current is 1 amp. The off to on and on to off response is usually around .1 millisecond. The two fuses on the system are not replaceable. These fuses are connected to the logic side status indicators and notify the user of problems.
The searchable product number of the 16 Point, 2 Common DC Powered Output Module is D3-16TD2. The product number of the instruction booklet is the D3-USER-M manual. Call us now to get pricing quotes and information about our warranties.