Frequently Asked Questions about 7V0ES108CD08
What does the diagnostic readout 001010 mean?
The diagnostic readout 001010 has a fault number of FL10 and a fault name of LNKFL, which is a serial link fault (communications failure) (L, T).
-The programmer card jumpers are set incorrectly.
-The baud rate is set incorrectly.
-8PL or 12PL is incorrectly connected or damaged.
-There is an Intermittent connection between 3TB32 (CTSA) and 12PL-7 or #TB41 (CTSB) and12PL-14.
What does the diagnostic readout 001011 mean?
The diagnostic readout 001011 has a fault number of FL11 and a fault name of DFPON, and is a delayed firing power on when it should be off (L, T)
-Q2 failed on -check test point DFP.
What does the diagnostic readout 001100 mean?
The diagnostic readout 001100 has a fault number of FL12 and a fault name of DFPOF and is a delayed firing power off when it should be on (L, T).
-Q2, Q3, R33 or U14 failed on the control card and it needs to be replaced.