Frequently Asked Questions about 7VPEX007CD04
What does the diagnostic readout 100011 mean?
The diagnostic readout 100011 has a fault number FL35 and a fault name O SPD which means the Motor running when RUN commanded (N, A).
-The RUN command was initiated during motor rotation.
-The ADR048-RSTOP is set too low.
-The ADR004-STPJP is not set properly for "flying restarts".
-The P7-SFB ZERO on the Process Interface card is misadjusted.
What does the diagnostic readout 100100 mean?
The diagnostic readout 100100 has a fault number FL36 and a fault name LNKER which means a bad message was detected on serial link by drive or other devices (N, A).
-There is excessive noise on 12PL-7 thru 14.
-The 12PL is incorrectly connected or damaged.
-The 5 VDC power supply is noisy.
-The baud rate is incorrectly set.
-Check the Process Interface card jumpers JP1, JP11, JP12, and JP13.
-The serial link checksum byte is incorrect.
What does the diagnostic readout 100101 mean?
The diagnostic readout 100101 has a fault number FL37 and a fault name IHUNG which means the armature current is zero when fully retarded (N, A).
-The P2-CFB ZERO on the Power Supply card is misadjusted.
-The DRPL is disconnected and damaged.
-The 1PL is disconnected or damaged.
-The current isolator has failed.
-The ADR080-CMFLM is set too high.
What does the diagnostic readout 100110 mean?
The diagnostic readout 100110 has a fault number FL38 and a fault name ELOCK which means there was an attempt to change software adjustments when soft locked (N, A).
-ADR033-DGNJP must be odd to program EEPROM.