About the 6KE$243005X1A1
The AF-300E$ drive family includes the General Electric Fuji Electric 6KE$243005X1A1 adjustable frequency drive. It accepts 3 phase power input. The required input voltage is 380-460V. The 6KE$243005X1A1 operates at 5 HP and the drive comes with a factory installed keypad. The drive is built with a UL Type 1 enclosure for safety and dependability. The power line frequency requirement is 50/60Hz.
Depending on your requirements, you can configure the keypad to display in English, Spanish, French,or Japanese. The keypad also provides remote input/output (I/O) status information. The keypad provides synchronous speed, torque voltage, output frequency, current, and line (machine speed) real-time information.
Standard features that the drive provides are restart after momentary power failure, bias frequency, torque limit control, energy saving selection, switch from line to inverter, slip compensation, multi-speed and acceleration and deceleration settings, and 3-jump frequencies.
If the voltage dips momentarily (input voltage dips below 310V), the drive can operate for 15 millisec with 85% of full load applied.
The dimensions of the 6KE$243005X1A1 are 10.24 in. H, 5.91 in. W, and 5.71 in. D. The weight of the 6KE$243005X1A1 drive 8.4lbs.
Fault conditions such as overcurrent, communication errors, motor overload, microprocessor errors, undervoltage, overheating, external fault, memory, and overvoltage are monitored by the drive and recorded in memory. The touchpad displays the faults and the drive retains the previous 3 faults to improve maintenance and assist with troubleshooting.