About the 6KF11H060X9A1
Fuji Electric is the maker of the 6KF11H060X9A1. The rated output current (A) is sixty. The overload rating (110% 1min) is sixty-six. The horsepower rating is forty. The drives dimensions are 21.7 (H) x 13.4 (W) x 10.0 (D) inches. A drive like the 6KF11H060 and above can be converted to external cooling simply by moving the upper and lower mounting brackets as shown in Fig. 2-2-3. Remove the M6 bracket screws, move the brackets, then secure the brackets using the M5 case mounting screws. (The bracket screws are no longer required after changing the bracket mounting position.) WARNING Always connect a ground wire. Electric shock or fire may result. Ensure that a trained specialist performs all wiring. Confirm that the power is turned off (open) before beginning any wiring operations. Electrical shock may result. Wait for a minimum of five minutes (6KF11L080, 6KF11H044 and below) or ten minutes (6KF11L115, 6KF11H060 and above) after power has been turned off (open) before starting the inspection. Also, confirm that the charge lamp is off and that DC voltage between terminals P(+) and N(-) does not exceed 25V. Electrical shock may result. Make sure that the Tightening torque and wire size for field wiring terminal are marked adjacent to the terminal or on the wiring diagram. Consult with the instruction manual for this drive from Fuji Electric. This instruction manual is titled the AF-300 F-11 and can be found online for easy access.
AX Control’s friendly and knowledgeable staff is available to assist you by phone or email.