The 6KG1143001X4B1 is a part of the Fuji Electric. For basic connection 1. Always connect power to the L1/R, L2/S, and L3/T main circuit power terminals on the drive. Connecting power to another terminal will damage the drive. Check that the power voltage is within the maximum allowable voltage marked on the nameplate, etc. 2. Always wire the ground terminal to ground to prevent problems such as fire or electric shock and to minimize noise. 3. Use a reliable crimp terminal for connection between a power terminal and a power wire. 4. After terminating the wiring connection, confirm the following: a. Confirm that the connection is correct. b. Confirm that all necessary connections have been made. c. Confirm that there is no short-circuit or ground fault between the terminals and wire. 5. Connection modification after power-on. The smoothing capacitor in the direct current portion of the main circuit cannot be discharged immediately after the power is turned off. To ensure safety, use a multimeter to check that the direct current (DC) voltage is lowered to the safety range (25V DC or less) after the charge lamp goes off. Also, confirm that the voltage is zero before short-circuiting. The residual voltage (electric charge) may cause sparks. WARNING Always connect a ground wire. Electric shock or fire may result. Ensure that a trained specialist performs all wiring. Confirm that the power is turned off (open) before beginning any wiring operations. Electrical shock may result.