About the 6KP1123001X1B1
Fuji Electric is the maker of the 6KP1123001X1B1. This drive is small with only one horsepower. The 6KP1123001X1B1has a 5.5 overload (110% 1min), a 5 rated output current (A), with one NEMA enclosure. The 6KP1123001X1B1 weighs in at 5.5 pounds and is 10.24 (H) x 4.33 (W) x 5.71 (D) inches. The 6KP1123001X1B1 has mounting screws of surface cover, keypad panel, a surface cover, a rating nameplate, and an intermediate cover. (1) Main circuit power terminals (L1/R, L2/S, L3/T) 1. Connect these terminals to the power supply via a molded-case circuit breaker or ground-leakage circuit breaker for circuit protection. Phase-sequence matching is unnecessary. 2. To ensure safety, a magnetic contactor should be used to disconnect the drive from the power supply when the drive protective function activates. 3. Use control circuit terminal FWD/REV or the RUN/STOP key on the keypad panel to start or stop the drive. The main circuit power should be used to start or stop the drive only if absolutely necessary and they should not be used more than once every hour. 4. If you need to connect these terminals to a single-phase power supply, please contact the factory. (2) Drive output terminals (U, V, W) 1. Connect these terminals to a 3-phase motor in the correct phase sequence. If the direction of motor rotation is incorrect, exchange any two of the U, V, and W phases. 2. Do not connect a power factor correction capacitor or surge absorber to the drive output. 3. If the cable from the drive to the motor is very long, a high-frequency current may be generated by stray capacitance between the cables and result in an overcurrent trip of the drive, an increase in leakage current, or a reduction in current indication precision.