About the 6KP1143100X9B1
The 6KP1143100X9B1 is a 3-Phase 100 HP General Electric AF-300 P11 Drive.
The 6KP1143100X9B1 is 460 VAC, 50/60 Hz, and 112 amp input. It has a 150 amp 119 KVA output. It can overload for 165 amps for 1 minute. It has a wattage loss of 1800 W @ 2 kHz and 2450 W @ 10 kHz. It is 97.8% efficient @ 2 kHz and 97.1% efficient @ 10 kHz. It is 26.6” tall, 14.8” wide, 10.6” thick, and 88 lbs. It should be used in temperatures between -10 to +40 degrees Celsius and between 5-95% humidity.
The 6KP1143100X9B1 is in an open-style chassis. Because of the open nature of this chassis, the drive should not be exposed to water or condensation, dust, direct sunlight, and corrosive or combustible gas. This drive should be installed vertically onto a metallic surface. Make sure that there is enough ventilation in the area this unit is going to be mounted so that the heat being generated in the area can be released. There are two cooling fans on the top of the drive that forces air into the internal circuitry of the drive.
The 6KP1143100X9B1 has a very basic external design. The only thing present on the front panel is a built-in user interface. The interface features an LCD display with LED indicators, a 4-digit 7-segment LED display, and a 9 key keypad panel. There are up/down arrow keys and keys that are labeled FWD, Stop, Reset, PRG, REV, FUNC/Data, and Shift >>. The display on the keypad monitors the operation status, function data, and diagnostics for the drive.