About the 269-10C-120

The 269-10C-120 is a motor management relay in the Multilin line manufactured by GE. The 269-10C-120 uses stator RTD temperature readings along with motor phase current readings to model the motor it is protecting. The 269-10C-120 monitors the mechanical load and motor for issues. With an optional GE Multilin meter (MPM) the module can also track power and voltages and perform tasks based on these values.

The 269-10C-120 includes these standard features:

  • microcomputer controlled

  • programmable on-site by keypad

  • 48-character alpha-numeric display

  • built-in "Help" functions

  • Self-check built into the relay circuitry

  • emergency restart capability

  • pre-trip alarm warnings

The 269-10C-120 can be used in a variety of settings, including for the protection of pumps, gears, and fans. It can protect compressors from overload. Using the undercurrent feature, the 269-10C-120 can protect pumps from loss of suction and fans from loss of air flow. The 269-10C-120 can also protect equipment and motors from operator abuse, and protect end users from shock hazards due to earth leakage current from moisture.

The front panel of the 269-10C-120 includes a backlit 48 character LCD display for viewing data, 4 LEDs that show when an output relay is in operation, 1 LED that indicates when a self-test alarm has been tripped, and a keypad for choosing actual values, to program setpoints, and to indicate causes of alarms and trips.

It is recommended the user mount the 269-10C-120 using 4 washers and 4 10-32 x 3/8" mounting screws. Although internal components have been shielded, the relay should be installed where it will not be affected by strong magnetic fields from high current conductors.

Frequently Asked Questions about 269-10C-120

What is the input power of the 269-10C-120 motor management Multilin relay?
The General Electric 269-10C-120 has an input power of 120 VAC listed. This motor management relay has an RTD composition of 10 Ohm copper wire. The maximum contact rating specifications are 250 VAC at 10 A resistive. WIth 1/4 HP the VAC is listed at 125 VAC and at 1/2 HP the VAC is 250.
What front view features does the Multilin General Electric 269-10C-120 digital motor management relay have?
The  General Electric 269-10C-120 Multilin motor management relay is similar to other 269 Multilins in the front display and front keypad configuration and capabilities. The key pad on the front cover allows the user to toggle up and down a page, line, or value, in addition to being able to clear, set, and store values. The keypad also allows the operator to view actual values, set points, and use a help feature for more information. 
What features are visualized by the rear view of the motor management 269 Multilin relay 269-10C-120?
The rear view of the GE Multilin 269-10C-120 motor management relay allows the user to view the Phase and Ground CT inputs at the bottom of the case. Each CT input has a 1A and a 5A side and lists the P/N. Each CT input is labeled as either phase 1, phase, 2, phase 3, or ground fault.

Reviews For 269-10C-120

Internal Review
(5.0)

This 269 Motor Management Relay from GE Multilin can be programmed on-site via the front display and keypad, or remotely via a connection to an external device. Read through manuals for additional details. --AX Control Tech Team.

Repair Services For 269-10C-120

Type Lead Time Price Action
Repair Service 1-2 weeks $1094

Our highly skilled technicians can repair your 269-10C-120. All of our repairs come with a 3 Year AX Control Warranty. Please contact us for additional information about our repair process. To receive the repair pricing and lead time listed above please process your repair order via our website. The following repair options may be available upon request:

  • 48-72hr Rush Repair
  • Detailed Repair Reports
  • AX Control Certificate of Warranty

AX Control Warranty Info

All products we sell are backed by our unparalleled warranty. A warranty certificate will be provided with your order upon request.
All PLCs, HMIs, and Turbine Control Boards: 3 Years
All AC/DC and Servo Drives: 2 Years
All Motors: 1 Year
Learn More