269PLUS-DO-100P-120

    Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures
  • 4.50 (2)
  • Click a star to rate this product
    Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures
  • 4.50 (2)
  • Click a star to rate this product
Adept at protecting motor systems, General Electric Multilin's 269PLUS-DO-100P-120 has the ability to "learn" acceleration time, cool-down rates, and more.

AVAILABILITY:

IN STOCK
SHIPS IN 3-5 DAYS

Sell Surplus: Have a 269PLUS-DO-100P-120 to sell? Sell Now
Exchange Credit: Learn more about our exchange credit program
  • Part Number: 269PLUS-DO-100P-120
  • SKU: 269PLUSDO100P120GM
  • Manufacturer: GE Multilin
  • Series: 269 Plus Motor Management Relay

269PLUS-DO-100P-120 Technical Specifications

Manufacturer General Electric Multilin (GE)
Manufacturer Location Ontario, Canada
Model Number 269PLUS-DO-100P-120
Software EnerVista 269
User Manual 1601-0013-E4
Shipping Dimensions 11.40" x 7.50" x 16.00"
Shipping Weight 7.75 lb.
Max. Power Consumption 20 VA
Dust/Moisture Protection NEMA 12/IP53 with proper installation
Pollution Degree II
Analog Current Output Isolation non-isolated, active source
Ground Fault Current Input Conversion calibrated RMS, sample time 2 ms
Communications Protocol Subset of Modbus® RTU

About the 269PLUS-DO-100P-120

General Electric Multilin's 269 PLUS relays are designed for adaptability to suit a range of AC motor protection applications. Relays in the 269 PLUS series have the ability to “learn” acceleration time, cool-down rates, and more. These values are continually updated, allowing the 269PLUS-DO-100P-120 to offer better protection for the individual motor.

These learned motor parameters are stored in the 269PLUS-DO-100P-120 relay’s non-volatile memory, so they remain intact even if control power is lost. Relay setpoints, motor statistical data, and pre-trip values are also stored in non-volatile memory.

Using a GE Multilin meter in conjunction with the 269PLUS-DO-100P-120 allows for monitoring voltage and power values, which in turn permits additional non-volatile memory protection functions based on Power Factor, voltage, kVars, and voltage sensed phase reversals.

269PLUS-DO-100P-120 is a Drawout version, which allows operators to remove the relay from service without shutting down the motor. There are a few differences between Drawout and Standard version relays. Drawout versions have only one set of alarm contacts, one set of Auxiliary 1 contacts, and one set of Auxiliary 2 contacts. They also do not meet CE compliance requirements. GE Multilin 269 Plus Motor Management Relay Instruction Manual 1601-0013-D3 provides more information on the differences between the two 269 PLUS relay versions, as well as installation and removal instructions.

Frequently Asked Questions about 269PLUS-DO-100P-120

What are some protection and control features of the Multilin 269PLUS-DO-100P-120 digital relay?
The 269PLUS-DO-100P-120 has a variety of features for protection and control of medium sized motors. The 269PLUS-DO-100P-120 has the ability to monitor multiple starts of the motor for analysis and detection. The motor management relay, 269PLUS-DO-100P-120, also has an emergency restart potential, with pre-trip warnings and alarms in the event of a potential trip. The 269PLUS-DO-100P-120 is able to monitor stator winding and bearing overtemperature with generation of overload curves and a user defined FlexCurve (TM). 
What are some monitoring and metering capabilities of the 269PLUS-DO-100P-120 Multilin GE 269 PLUS digital motor management relay?
The 269PLUS-DO-100P-120 Multilin GE 269 PLUS is able to meter current and thermal capacity. This Multilin 269 PLUS has the capacity to generate learned and statistically recorded data. The relay includes an optional voltage and power metering capability. Finally the data logger feature is useful to the user to aid in management of a specific medium sized AC motor. 
What composition is the RTD of the 269PLUS-DO-100P-120 Multilin digital GE relay?
The 269PLUS-DO-100P-120 Multilin digital GE relay for motor management has a 100P RTD. This specification indicates that the RTDs within the 269PLUS-DO-100P-120 Multilin are composed of 100 platinum Ohm.

Reviews For 269PLUS-DO-100P-120

Internal Review
(4.0)

General Electric Multilin’s 269PLUS-DO-100P-120 protects and manages motor systems with ease. However, users should be aware that the keypad and LCD are prone to occasional downtime; AX Control will ensure all units are in optimal working condition when sent out and can repair any units experiencing suboptimal performance. - AX Control Tech

Repair Services For 269PLUS-DO-100P-120

Type Lead Time Price Action
Repair Service 1-2 weeks $1151

Our highly skilled technicians can repair your 269PLUS-DO-100P-120. All of our repairs come with a 3 Year AX Control Warranty. Please contact us for additional information about our repair process. To receive the repair pricing and lead time listed above please process your repair order via our website. The following repair options may be available upon request:

  • 48-72hr Rush Repair
  • Detailed Repair Reports
  • AX Control Certificate of Warranty

AX Control Warranty Info

All products we sell are backed by our unparalleled warranty. A warranty certificate will be provided with your order upon request.
All PLCs, HMIs, and Turbine Control Boards: 3 Years
All AC/DC and Servo Drives: 2 Years
All Motors: 1 Year
Learn More