According to the O character in the 565-5-5-O-B order code, this relay has an optional card and will operate on a direct current voltage of 20-60. This model can accept inputs from a variety of 4 to 20 mA sources which can provide trip signals.

AVAILABILITY:

CALL FOR AVAILABILITY

Sell Surplus: Have a 565-5-5-O-B to sell? Sell Now
Exchange Credit: Learn more about our exchange credit program
  • Part Number: 565-5-5-O-B
  • SKU: 56555OBGM
  • Manufacturer: GE Multilin
  • Series: 565/575 Feeder Management Relay

565-5-5-O-B Technical Specifications

Manufacturer General Electric Multilin (GE)
Model Number 565-5-5-O-B
Measurements Response RMS Responding
Phase Current Inputs Saturation 20 Times CT
Storage Temperature -30 to 80 °C
Undervoltage Alarm and Trip Delay 0.1 to 25.5 seconds in Steps of 0.1 Seconds
Unit Weight Approx. 20 lbs
Voltage Inputs VT Burden Less than 0.2 VA at Rated Input
Voltage Supply 20-60 VDC
Ground Current Input CT Primary 10-5000 Amps in 5 Amp Steps
Max Voltage for Analog Outputs 30 VDC or p-pAC

About the 565-5-5-O-B

565-5-5-O-B is a digital feeder management relay that is manufactured by GE Multilin. This relay has a phase CT rating of 5 amps and a ground CT rating of 5 amps. The control volts are 20-60 VDC. This unit includes an option card that provides breaker trip coil supervision, breaker discrepancy, printer driver, and an MTM communications port.

In Setpoints Mode, there are a number of setpoints for the user to configure. The Configuration setpoints on this relay include the clock, the switch contact functions, the switch contact configurations, the relay assignments, the breaker response delay, the breaker discrepancy delay, the trip coil supervision, the accumulated KA, the event recording, the event printing, the cold load P/U delay, and the MTM communications enable. The Calibration Mode setpoints on this relay include the exercise relay, the status of the switch inputs, the LCD display contrast, and the Multilin 565 Relay Revision. The Voltage setpoints on this relay include the VT connection, the VT nominal secondary volts, the VT primary volts, the zero volts detect, the undervoltage trip, the undervoltage alarm, the overvoltage trip, and the overvoltage alarm. The Demand Metering setpoints on this relay include the amps demand, the KW demand, and the KVAR demand. The Communications setpoints include the relay address and the baud rate. The Analog Output setpoints include the analog output parameters and the analog output range. The Analog Input setpoints include the analog input title and units, the minimum and maximum current scale values, the analog input trip, and the analog input alarm.

Frequently Asked Questions about 565-5-5-O-B

What does the B option afford the 565-5-5-O-B when compared to the A option of the Multilin 565 feeder protection relay series?
The A or the B option found as the last numeric of the part sequence of a Multilin model 565 feeder protection relay specifies the control volt range of the relay. For example, option A reflects that the relay has a control voltage range of 90 to 260 VAC or 95 to 280 VDC. Option B in contrast shows that the base model 565 Multilin has a control voltage range from 20 to 60 VDC.
What does the option card add to the base model 565 Multilin feeder protection relay, specifically for the 565-5-5-O-B field programmable relay?
The 565-5-5-O-B field programmable protection relay is a relay of the 565 Multilin series. This additional option card (option O) allows the unit an additional breaker trip coil supervision feature. Additionally this option card provides a greaker discrepancy and a printer driver to the unit as well as a MTM communications port. 
What are the input and output specifications of the 565 Multilin feeder protection relays?
These relays have a set of 'analog select' inputs which can be connected to a PLC. Thse inputs can either be used as an indication of breaker status or to indicate external trips. The feeder protection relay has size electromechanical output relays. The name of each output is as follows: close, trip, aux 1, 2, 3, and 4. 

Reviews For 565-5-5-O-B

Internal Review
(5.0)

If you are using a device that operates strictly on a direct current rather than an alternating current the 565-5-5-O-B relay is the perfect model to purchase. - AX Control Technician

Repair Services For 565-5-5-O-B

Type Lead Time Price Action
Repair Service 1-2 weeks $1524

Our highly skilled technicians can repair your 565-5-5-O-B. All of our repairs come with a 3 Year AX Control Warranty. Please contact us for additional information about our repair process. To receive the repair pricing and lead time listed above please process your repair order via our website. The following repair options may be available upon request:

  • 48-72hr Rush Repair
  • Detailed Repair Reports
  • AX Control Certificate of Warranty

AX Control Warranty Info

All products we sell are backed by our unparalleled warranty. A warranty certificate will be provided with your order upon request.
All PLCs, HMIs, and Turbine Control Boards: 3 Years
All AC/DC and Servo Drives: 2 Years
All Motors: 1 Year
Learn More