The 565-5-5-O-A model is the first relay in the 565 Series that has the option card used for printer driving, breaker discrepancy, and breaker trip coil supervision. This relay is also equipped with RMS responding.

AVAILABILITY:

IN STOCK
SHIPS IN 3-5 DAYS

Sell Surplus: Have a 565-5-5-O-A to sell? Sell Now
Exchange Credit: Learn more about our exchange credit program
  • Part Number: 565-5-5-O-A
  • SKU: 56555OAGM
  • Manufacturer: GE Multilin
  • Series: 565/575 Feeder Management Relay

565-5-5-O-A Technical Specifications

Manufacturer General Electric Multilin (GE)
Manufacturing Location Markham, Ontario, Canada
Model Number 565-5-5-O-A
Maximum Power Supply 50 Watts
Measurements Bandwidth 0-120 Hz
Phase Overcurrent Protection Timed Overcurrent Pickup Range 25-250% of CT in Steps of 1%
Undervoltage Alarm and Trip Pickup 101 to 125% in steps of 1%
Weight Approximately 20 lbs.
Burn In Temperature 60°C for 24 Hours
Ground Current Input Momentary 20 x CT Input Rating for 3 Seconds
Ground Overcurrent Protection Time Dial 32 Selections

About the 565-5-5-O-A

565-5-5-O-A is a digital feeder management relay that is manufactured by GE Multilin. This relay has a phase CT rating of 5 amps and a ground CT rating of 5 amps. The control volts are 90-260 VAC and 95-280 VDC. This unit includes an option card that provides breaker trip coil supervision, breaker discrepancy, printer driver, and an MTM communications port.

In Setpoints Mode, there are a number of setpoints for the user to configure on the relay. The Phase Current setpoints on this relay include the phase CT primary rating, the phase overcurrent pickup level, the phase overcurrent curve shape, the phase overcurrent time dial, the phase overcurrent trip relay, the phase overcurrent alarm, the phase instantaneous trip, and the phase custom curve trip times. The Ground Current setpoints on this relay include the ground sensing system, the ground CT primary rating, the ground overcurrent pickup level, the ground overcurrent curve shape, the ground overcurrent time dial, the ground overcurrent trip relay, the ground overcurrent alarm, the ground instantaneous trip, and the ground custom curve trip times. The User Level setpoints include the user level and the security feature/access code. The MTM Metering setpoints include the MTM communications alarm, the MTM CT select, the MTM CT primary rating, the power factor alarm, the power factor trip, the frequency alarm, the frequency trip, the MTM scaling factor, and the voltage reversal trip. The Demand Metering setpoints on this relay include the amps demand, the KW demand, and the KVAR demand.

Frequently Asked Questions about 565-5-5-O-A

What are the features and characteristics of the Multilin 565 feeder protection relay?
The Multilin 565-5-5-O-A is a feeder protection relay of the Multilin 565/575 series. This relay is made to provide protection during all operating conditions. The relay is able to monitor feeder phase currents and ground currents to provide complete and accurate time/overcurrent phase and ground protection. The trip set points for overcurrent phase and ground current of the 565-5-5-O-A are programmed by taking into consideration a wide variety of industry standard moderately inverse, normal inverse, extremely inverse, and very inverse curves. If these standard curves are not applicable there is also the option to use a progammable custom curve by entering specific data to generate the custom curve. 
What are the ordering specifications of the different Multilin 565 feeder management relays and specifically the 565-5-5-O-A?
The 565-5-5-O-A has specific ordering designations as indicated by the alpha-numeric selections listed following the parent 565 Multilin base part number and series indicator. The first number following the base indicates the Phase CT rating of the relay. In this case, the 5 indicates that this relay has a phase CT rating of 5 amps. Similarly, the next numeric (5) shows that this feeder protection relay has a ground CT rating of 5 amps. The other option for each order specification is 1 amp for phase and ground CT rating. Finally, the O option designates an additional option care providing breaker trip coil supervision, breaker discrepancy, and an MTM communications port. The A designation shows that the control voltage for this unit is 90 to 260 VAC or 95 to 280 VDC compared to the B option.
 

Reviews For 565-5-5-O-A

Internal Review
(5.0)

One of the primary reasons that this model should be purchased is because of the option card. The option card provides additional breaker discrepancy, printer driver, and breaker trip could supervision features. - AX Control Technician

Repair Services For 565-5-5-O-A

Type Lead Time Price Action
Repair Service 1-2 weeks $1755

Our highly skilled technicians can repair your 565-5-5-O-A. All of our repairs come with a 3 Year AX Control Warranty. Please contact us for additional information about our repair process. To receive the repair pricing and lead time listed above please process your repair order via our website. The following repair options may be available upon request: