About the FN-PC10LD41
The Pro-face FN-PC10LD41 (Alternate Model # 2980051-03 ) is designed to be used with GP3000 Series, GLC2000 Series, and LT Series as a Flex Network single-axis positioning unit. It is used for parameter entry, as well as positioning check and movement, alternatively called a Remote I/O Unit.
Some of the FN-PC10LD41 specifications are as follows:
- Dimensions are W 122 x H 196 x D 35mm [4.80 x 7.72 x 1.38in.]
- Passive air-cooling
- Input voltage is DC24V
- Power consumption is 4.5W or less
- IEC61131-2 (JIS B 3501) compliant
- IP30 protection
- weight before packaging is 700g
More specific electrical standards for this unit include, a required ambient operating temperature of 0° to 55°C. The rated voltage is DC24V and the rated voltage range is DC20.4V to DC28.8V. The maximum allowable voltage input is DC26.4V. It has 5 input points and input ON voltage of DC19V or higher, the input OFF voltage being 5V or less. The input impedance is 3.9kΩ. The input delay (off-on and on-off) is 1.5m or less. The storage temperature is -25° to +70°C and the ambient humidity is 30%RH to 95%RH (no condensation).
Technicians have advised that, to prevent malfunctions due to noise in FN-PC10LD41 host devices, communication cables must be wired separately from high-frequency lines and power lines such as high-voltage lines, high-current lines, and inverters