FN-PC10LD41

    Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures
  • 4.6 (6)
  • Click a star to rate this product
    Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures
  • 4.6 (6)
  • Click a star to rate this product
The Pro-face Flex Network Single-Axis Positioning Unit FN-PC10LD41 is designed to be used with GLC, LT, and GP3000 Series as a remote I/O System.

AVAILABILITY:

CALL FOR AVAILABILITY

Sell Surplus: Have a FN-PC10LD41 to sell? Sell Now
Exchange Credit: Learn more about our exchange credit program
  • Part Number: FN-PC10LD41
  • SKU: FNPC10LD41PX
  • Manufacturer: Pro-face Xycom
  • Series: Flex Network Series

FN-PC10LD41 Technical Specifications

Dimensions W 122 x H 196 x D 35mm [4.80 x 7.72 x 1.38in.]
Features Passive Air Cooling
Input Voltage DC24V
Manufacturer Pro-Face
Model Number 2980051-03
Power Consumption 4.5W or Less
Product Type Flex Network Single Axis Positioning Unit
Standards IEC61131-2 (JIS B 3501) compliant. IP30 Protection
Weight Approx. 700g

About the FN-PC10LD41

The Pro-face FN-PC10LD41 (Alternate Model # 2980051-03 ) is designed to be used with GP3000 Series, GLC2000 Series, and LT Series as a Flex Network single-axis positioning unit.  It is used for parameter entry, as well as positioning check and movement, alternatively called a Remote I/O Unit.

Some of the FN-PC10LD41 specifications are as follows:

  • Dimensions are W 122 x H 196 x D 35mm [4.80 x 7.72 x 1.38in.]
  • Passive air-cooling
  • Input voltage is DC24V
  • Power consumption is 4.5W or less
  • IEC61131-2 (JIS B 3501) compliant
  • IP30 protection
  • weight before packaging is 700g

More specific electrical standards for this unit include, a required ambient operating temperature of 0° to 55°C. The rated voltage is DC24V and the rated voltage range is DC20.4V to DC28.8V. The maximum allowable voltage input is DC26.4V. It has 5 input points and input ON voltage of DC19V or higher, the input OFF voltage being 5V or less. The input impedance is 3.9kΩ. The input delay (off-on and on-off) is 1.5m or less. The storage temperature is -25° to +70°C and the ambient humidity is 30%RH to 95%RH (no condensation).

Technicians have advised that, to prevent malfunctions due to noise in FN-PC10LD41 host devices, communication cables must be wired separately from high-frequency lines and power lines such as high-voltage lines, high-current lines, and inverters

Reviews For FN-PC10LD41

Internal Review
(5.0)

To prevent malfunctions due to noise in FN-PC10LD41 host devices, communication cables must be wired separately from high-frequency lines and power lines such as high-voltage lines, high-current lines, and inverters. - AX Control Technicians

Repair Services For FN-PC10LD41

Type Lead Time Price Action
Repair Service 1-2 weeks $575

Our highly skilled technicians can repair your FN-PC10LD41. All of our repairs come with a 3 Year AX Control Warranty. Please contact us for additional information about our repair process. To receive the repair pricing and lead time listed above please process your repair order via our website. The following repair options may be available upon request:

  • 48-72hr Rush Repair
  • Detailed Repair Reports
  • AX Control Certificate of Warranty

AX Control Warranty Info

All products we sell are backed by our unparalleled warranty. A warranty certificate will be provided with your order upon request.
All PLCs, HMIs, and Turbine Control Boards: 3 Years
All AC/DC and Servo Drives: 2 Years
All Motors: 1 Year
Learn More