50V4150

    Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures
  • 5.00 (3)
  • Click a star to rate this product
    Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures
  • 5.00 (3)
  • Click a star to rate this product
50V4150 50HP 460V AC Drive today

AVAILABILITY:

IN STOCK
SHIPS TODAY

Sell Surplus: Have a 50V4150 to sell? Sell Now
Exchange Credit: Learn more about our exchange credit program
  • Part Number: 50V4150
  • SKU: 50V4150RE
  • Manufacturer: Reliance Electric
  • Series: GV3000 Drives

50V4150 Technical Specifications

Manufacturer Reliance Electric
Series GV3000
Part Number 50V4150
HP 50 HP
Input Voltage 380-460 VAC
Enclosure Type 1/IP20
Keypad/Display Built-In Keypad
Phase 3 Phase
kW 37.3kW
Hz 50/60Hz
Instruction Manual D2-3339 & D2-3340

About the 50V4150

The 50V4150 is a GV3000 Series Power Module. It was originally designed by Reliance Electric but could have also been mass-produced by Baldor Reliance and ABB. None of these companies offer any type of support for the 50V4150. It may be a little difficult to find but AX Control still tries to keep it in stock.

This drive is 50HP 380-460V with an input of 57.3 KVA. It has an input of 72 amps and output amps that are 8 kHz and 67 amps. It has a power loss of 1200 watts. This module has the ability to select either vector or V/Hz regulation.

The 50V4150 is protected by a NEMA 1 rated enclosure. This enclosure contains vents along its sides and has a small door on the front that can allow for access to an RS-232 serial connection port that goes to the regulator board.  This enclosure is only meant for inside applications. It should be mounted onto a panel or another flat metallic surface. This device should be kept away from corrosive or combustible materials. It is not considered to be dust or drip-tight so the area it is mounted to should be kept free from liquids or dust.

There are several important components that make up the 50V4150. These components include a keypad with attached bracket assembly, regulator board, power board, bus capacitors, gate driver board, power supply, a fan and internal fan assembly system, diode bridge, wire harness, and IGBT module. The regulator board connects to the built-in keypad using the wire bracket that is attached to it.  

Frequently Asked Questions about 50V4150

How many input and output amps does 50V4150 have?
50V4150 has 72 input amps. 50V4150 has 67 output amps. 50V4150's output amps are when 50V4150 is operating at 8 kHz carrier frequency.
What are the power module specific fault codes on 50V4150?
The power module specific fault code errors on 50V4150 are fault codes PUc and PUn. Fault code PUc on 50V4150 is the fault code error for a missing power module ID connector. This fault on 50V4150 is caused by a bad or disconnected cable between 50V4150 regulator and 50V4150 module. Fault code PUn is the fault code error on 50V4150 for power module not identified. This fault on 50V4150 occurs when drive parameters are restored to power-up defaults on 50V4150. When this fault occurs on 50V4150, the regulator has not been configured to match the 50V4150 power module.
What terminals does the A-C input power wiring connect to on 50V4150?
The A-C input power wiring on 50V4150 connects to terminals R/L1, S/L2, and TL3 on 50V4150.
Which manuals are used with 50V4150?
There are two primary manuals used with 50V4150. The manuals are the software and hardware manuals for 50V4150, manuals D2-3339 and D2-3340, respectively. Though the manuals aren't specific to 50V4150, the manuals identify 50V4150, and the manuals are specific to Reliance GV3000 Power Modules.

Repair Services For 50V4150

Type Lead Time Price Action
Repair Service 1-2 weeks $1587

Our highly skilled technicians can repair your 50V4150. All of our repairs come with a 3 Year AX Control Warranty. Please contact us for additional information about our repair process. To receive the repair pricing and lead time listed above please process your repair order via our website. The following repair options may be available upon request:

  • 48-72hr Rush Repair
  • Detailed Repair Reports
  • AX Control Certificate of Warranty

AX Control Warranty Info

All products we sell are backed by our unparalleled warranty. A warranty certificate will be provided with your order upon request.
All PLCs, HMIs, and Turbine Control Boards: 3 Years
All AC/DC and Servo Drives: 2 Years
All Motors: 1 Year
Learn More