About the 6V41-248TA
6V41-248TA is a GV6000 AC Drive that is manufactured by Reliance Electric. The nominal duty horsepower is 200, the continuous amps are 248, and the frame is 6. The dimensions of frame 6 are 403.9 mm x 850 mm x 275 mm x 300 mm x 825 mm. This drive has a 460 VAC input and is enclosed in a NEMA 1 enclosure. A braking transistor comes standard on this unit. The I/O is 24 VDC.
There are a number of fault codes on the drive. Fault number 24 is a deceleration inhibit fault, which means that the drive is attempting to limit bus voltage by not following the deceleration command. Fault number 25 is an overspeed limit fault. Increase the overspeed limit or remove excessive load from the motor. Fault number 29 is an analog input loss fault, which means that a signal loss has occurred. To fix this fault, check the drive parameters and check for broken/loose connections at inputs. Fault number 33 is an auto restart tries fault, which means that the drive unsuccessfully attempted to reset a fault. To correct this fault, manually clear all faults. Fault number 36 is an SW overcurrent fault, which means that the drive output current has exceeded the current allowed on the software. Check for excess load and an improper DC boost setting. Fault number 48 is a parameters defaulted fault, which means that the user commanded the drive to write default values to EEPROM. To fix this fault, clear it manually, cycle power to the drive, or program the drive parameters manually.