E03-2

    Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures
  • 4.70 (10)
  • Click a star to rate this product
    Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures
  • 4.70 (10)
  • Click a star to rate this product
E03-2 is a PowerLogic Enhanced Enercept Meter

AVAILABILITY:

IN STOCK
SHIPS IN 3-5 DAYS

Sell Surplus: Have a E03-2 to sell? Sell Now
Exchange Credit: Learn more about our exchange credit program
  • Part Number: E03-2
  • SKU: E032SD
  • Manufacturer: Square D
  • Series: PowerLogic 3020

About the E03-2

The E03-2 is an enhanced Enercept Meter in the PowerLogic line by SquareD (Schneider Electric.) The E03-2 is an economical solution for energy metering applications. The E03-2 is designed with three interconnected split core CTs. One of these CTs has built-in communication and metering electronics. The E03-2 can deliver up to 26 parameters, including energy, power, volts, demand, amps, power factor and reactive power. The E03-2 may be used on both single-phase systems as well as on three-phase systems.

The E03-2 provides ANSI C12.1 metering accuracy. It is UL listed and cUL listed. The E03-2 is designed for simple, inexpensive "snap in" installation without the need for a separate meter enclosure. However, safety precautions must be observed during installation.

The E03-2 comes standard with Modbus RTU 2-wire protocols (RS-485.) It is compatible with other PowerLogic devices and can utilize the same communication network. Transferred data from the E03-2 may be shown in tabular or graphical format.

The E03-2 is designed with the following parts:

  • Voltage leads (3)

  • Mandatory fuse per NEC.

  • Modbus RS-485 Connector

  • Status-LED

  • Address Selection Switches

  • External CTs

  • Neutral Lead

The Status LED will blink green when the E03-2 is working normally. If the LED is blinking slowly in red, wiring may be incorrect. If the LED is blinking quickly in red the CT's max current rating has been exceeded.

The E03-2 is rated 208-480 Vac line-to-line. 50/60 Hz frequency. 100 mA. Operating temperature range is 0 to +60 degrees Celsius (+32 to +140 degrees Fahrenheit) in 0-95% relative humidity, non-condensing.

Repair Services For E03-2

Type Lead Time Price Action
Repair Service 1-2 weeks $953

Our highly skilled technicians can repair your E03-2. All of our repairs come with a 3 Year AX Control Warranty. Please contact us for additional information about our repair process. To receive the repair pricing and lead time listed above please process your repair order via our website. The following repair options may be available upon request:

  • 48-72hr Rush Repair
  • Detailed Repair Reports
  • AX Control Certificate of Warranty

AX Control Warranty Info

All products we sell are backed by our unparalleled warranty. A warranty certificate will be provided with your order upon request.
All PLCs, HMIs, and Turbine Control Boards: 3 Years
All AC/DC and Servo Drives: 2 Years
All Motors: 1 Year
Learn More

E03-2 Manuals, White Papers, Data Sheets, and Troubleshooting