IOM-44 is a PowerLogic I/O module

AVAILABILITY:

IN STOCK
SHIPS TODAY

Sell Surplus: Have a IOM-44 to sell? Sell Now
Exchange Credit: Learn more about our exchange credit program
  • Part Number: IOM-44
  • SKU: IOM44SD
  • Manufacturer: Square D
  • Series: PowerLogic 3020

Product Description

The IOM-44, manufactured by Square D (Schneider Electric) in their PowerLogic line, is an I/O (Input/Output) module designed with the capability to allow MicroLogic 'full function' circuit breaker units to be linked together within a larger PowerLogic network.

The IOM-44 has four inputs and four outputs. One of the outputs is a solid-state KYZ relay that is rated 240VAC and 300VDC. This output has a maximum rating of 96mA. The KYZ relay is needed for any pulse applications. The KYZ relay is a Form-C relay. This relay is best used with very low burdens.

Three of the other outputs are also Form-C 10A mechanical relays. 10 amp relays have a limited life of about 10 million operations under no load or 100,000 operations under a load. Between these two types of outputs, the IOM-44 has the ability to detect over 100 alarm conditions. It can have more than one alarm condition assigned to one relay, once setpoints have been defined.

The Form-C 10A mechanical relays can be set up for mechanical tasks such as annunciating alarms or opening and closing circuit breakers. Mechanical outputs can be configured thusly:

  • Normal

  • Latched (electrically held)

  • Timed

  • Absolute kVArH pulse

  • Absolute kWH pulse

  • kVar out pulse

  • kWH out pulse

  • kVARH in pulse

  • kWH in pulse

  • kVAH pulse

It is worth noting the last seven modes in the above list are for pulse initiator applications, which should only be set up on the solid-state KYZ output. 

The IOM-44 flush-mounts with four screws, distributed equally at the top and bottom corners of the module.

The current range for circuit monitor inputs is 0–7.4 A ac, and the nominal current is 5 A ac. For the circuit monitor voltage inputs for each channel, the voltage range is 0-180 VAC, and the typical nominal voltage is 120 VAC. For the control power input specifications, the AC input range is 100-264 VAC, the frequency range is 47-440 Hz, the typical burden is 14-19 VA, and the DC input range is 100-350 VDC.

Repair Services For IOM-44

Type Lead Time Price Action
Repair Service 1-2 weeks $1005

Our highly skilled technicians can repair your IOM-44. All of our repairs come with a 3 Year AX Control Warranty. Please contact us for additional information about our repair process. To receive the repair pricing and lead time listed above please process your repair order via our website. The following repair options may be available upon request:

  • 48-72hr Rush Repair
  • Detailed Repair Reports
  • AX Control Certificate of Warranty

AX Control Warranty Info

All products we sell are backed by our unparalleled warranty. A warranty certificate will be provided with your order upon request.
All PLCs, HMIs, and Turbine Control Boards: 3 Years
All AC/DC and Servo Drives: 2 Years
All Motors: 1 Year
Learn More

IOM-44 Manuals, White Papers, Data Sheets, and Troubleshooting