About the 8030-PS-25
The 8030-PS-25 is a part of the SY/MAX. The 8030-PS-25 can be installed in a few different ways such as in any register slot of an SY/MACK rack, on the side of an SY/MAX rack, using the ADP100 Adapter Plate and CC15 Power Supply Cable, or in a standalone configuration, using the Adapter Plate CC15 Power Supply Cable. The input voltage range at 47-63 Hz is a 102-132 VAC. The input power consumption is 175 VA nominal. The power loss ride through at full rated load is 16ms minimum at 102/204 VAC. The approx. I/O Capacity is 128. The specific output voltage range is 5.12-5.20 VDC. The output voltage (nominal) is +5VDC. The output current capacity at 40°C is 12 Amps DC (0.6 Amps DC for battery bus). The output current capacity at 50°C is 10 Amps DC (0.6 Amps DC for battery bus). The output current capacity at 60°C is 8 Amps DC (0.6 Amps DC for battery bus). The weight in pounds is 3.9 and in kg is 1.8 (ADP 100 optional). There are LED indicator lights that are +5 VDC (Battery low). During Undervoltage lockout when the output voltage is below normal operating range, under voltage lockout circuit shuts down the regulator. The overvoltage lockout is 5.75 V min.; 6.25 V nominal; 6.75 V max. cycle power reset. For additional information refer to the SY/MAX Instruction Bulletin. This instructional bulletin provides detailed information in regard to this product.